Description

Graphic LCD Display

Text and mnemonic diagrams displaying operating modes, system parameters, and alarm signals.

Connection 10/100 BaseT

The availability of detailed information on battery runtime, load level, and technical condition indicators facilitates timely replacement, reducing the risk of downtime.

Energy-saving mode of the UPS, protected by a patent application

When quality power is supplied from the external network, the UPS operates in a mode that consumes less energy (by not utilizing some internal modules), enhancing its energy efficiency without compromising the quality of protection for connected equipment.

Battery failure notification

Advance notification of impending battery failure allows for timely preventive maintenance.

Automatic internal bypass

In case of overload or UPS failure, the load is switched to power from the electrical network.

Scalability of battery runtime

If necessary, it allows for a quick increase in backup time.

Intelligent battery management

Maximizes battery efficiency, extends its lifespan, and enhances reliability through precise intelligent charging.

Battery replacement during UPS operation

Ensures that protected equipment receives clean sine wave power during battery replacement.

Automatic restart of connected loads after UPS shutdown

Automatically starts connected equipment after network power is restored.

Battery charging with temperature compensation

Extends battery life by adjusting the charging voltage according to battery temperature.

UPS management via local network

Allows remote management of the UPS over the network.

Compatible with InfraStruXure Manager

Enables centralized management using APC InfraStruXure Manager.

SmartSlot connector

The use of control cards allows modification of the UPS's capabilities.

LED status indicators

Visual indicators quickly provide an overview of the device and power status.

Connection via serial port

Management of the UPS through the serial port.

External batteries connected via Plug-and-Play

Ensures protected equipment receives sine wave power during the connection of additional batteries to the UPS.

Converted between tower/chassis configurations for installation in equipment racks

Protects initial investments in the UPS when transitioning from a vertical UPS to rack-mounted UPS.

Hot-swappable battery replacement

Possibility of connecting an external battery pack

Management

Communication interface with PC RS-232/RJ-45/SmartSlot

Specifications

UPS Type: Double Conversion (on-line)

Application: For home, for computer

Output Power

Volt-amperes: 10000 VA

Watts: 10000 W

Input Network Parameters

Nominal Voltage: 230/400 V (3 phases)

Minimum Voltage (for operation from 220V network): 160 V

Maximum Voltage (for operation from 220V network): 275 V

Frequency: 50/60 Hz

Frequency Deviation Range: ± 20% (10 Hz)

Output Parameters

Nominal Voltage: 230 V (± 3%)

Frequency: 50/60 Hz (± 3 Hz)

Efficiency at Full Load: 94.6% (at 50% load: 95%)

Transfer Time: ms (continuous)

Battery Parameters

DC Voltage: 96 V (8x 12 V)

Charging Time: 1.5 hours

Runtime at Max Load: 3.8 min. (at 50% load: 11.5 minutes)

Ability to connect additional batteries: + (up to two sets)

Filtering and Protection

Wired (computer) network protection: + (RJ-45)

Telephone line protection: + (RJ-45)

Surge suppression: 480 J

Overload protection: +

Overvoltage protection: +

Battery deep discharge protection: +

Connectors

PC connection interface: USB

SmartSlot: 1 pc.

Input Connectors: Hard Wire 3 wire (1PH+N+G), Hard Wire 5-wire (3PH+N+G), RJ-45

Output Connectors: (1) Hard Wire 3-wire (HN + G), (6) IEC 320-C13, (4) IEC 320-C19, (3) IEC Jumpers, RJ-45

Physical Characteristics

Width: 263 mm

Height: 432 mm

Depth: 715 mm

Weight: 111.82 kg (gross: 126.82 kg)

Additional Characteristics

Topology: Double Conversion (Peak Factor 03:01)

Bypass: Internal (with automatic or manual activation)

Battery Type: Sealed lead-acid battery, maintenance-free, with gelled electrolyte: leak-proof

Emergency Power Off (EPO)

Voltage waveform type: Pure sine wave

Operation

Variable (set) input voltage range: 100-275 V (50% load) - at 230 V / 173-476 V (50% load) – at 400 V

Control Panel: Multifunctional control and management console with LCD display

Audible and visual signals with a priority system based on the severity of the event

Operating range of environmental parameters: 0-40°C

Operating range of relative humidity: 0-95%

Operating altitude range: 0-3000 meters

Storage temperature: -15...+45°C

Relative humidity during storage: 0-95%

Storage altitude: 0-15000 meters

Acoustic noise level at a distance of 1 meter from the device surface: 55.00 dB(A)

Heat dissipation in network operation mode: 1497.00 BTU/hour

Protection class: IP 20

Package includes:

UPS

Power cord

Software CD

Documentation CD

Installation guide

Temperature sensor

USB cable

Web/SNMP Management Card

```

Specifications
Manufacturer
UPS
Model
UPS APC Smart-UPS SRT 10000VA
Product documents and safety information
Manufacturer
UPS
Safety information
Available on request from info@farkasltd.com before you submit your request.
Warranty and returns

Consumers have legal rights if goods are faulty, separate from any manufacturer warranty. See Warranty and Returns & Refunds. To withdraw from a purchase use Withdraw from contract.